Viconics VWZS Integration Guide Manual do Utilizador Página 8

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 70
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 7
8
Any given device / node / controller including the Jace coordinator can ONLY give a
maximum 6 ZigBee addresses out to other devices so they join the active ZigBee network.
This means for any device / node / controller to be able to successfully join a ZigBee network,
it needs an address to be assigned by another device / node / controller which is within
connectivity and that has NOT already assigned its maximum of 6 addresses allowed.
Please note that once a device / node / controller has been assigned a ZigBee address & has
joined the active ZigBee network, it will save its assigned ZigBee address to flash memory &
re-use it afterwards even after a power failure or a network re-start. The ONLY time device /
node / controller would require a NEW ZigBee address is if the network is re-started with
either a new PAN ID or a new Channel value. This causes the currently assigned & saved
ZigBee address in flash to be erased & will force the / node / controller to try to re-join a new
network.
Vista de página 7
1 2 3 4 5 6 7 8 9 10 11 12 13 ... 69 70

Comentários a estes Manuais

Sem comentários