Viconics BACnet Zoning System Engineering Guide
Specification
Vista de página 0
1 2 3 4 5 6 ... 11 12

Resumo do Conteúdo

Página 1 - Specification

Viconics BACnet Zoning System Engineering Guide Specification

Página 2

Sequence of Operation – The Viconics BACnet Zoning System shall operate in the following manner: 1. The VZ7656x1000B Rooftop Unit controller sha

Página 3

Sequence for economizer on VZ7656E1000B only: The fresh air damper can be controlled through more than one sequence to achieve different control st

Página 4

Economizer Mode and CO2 Level Control If the fresh air damper is to be used for both free cooling and CO2level control (economizer mode and CO2 lev

Página 5

Viconics BACnet Zoning System Engineering Guide Spec 1.01 System Description – The Viconics BACnet Zoning System (VBZS) shall provide a simple

Página 6

(4000 feet), repeaters shall be used to ensure proper communication. With repeaters and a BACnet MS_TP supervisory system, the maximum number of no

Página 7

VZ7656x1000B BACnet Rooftop or Heat Pump Controller The Rooftop unit Controller shall be: VZ7656R1000B: Up to two heating and two cool stages, si

Página 8

The controller shall be capable of operating the packaged unit even if there is a loss of communication with the zone controllers. The packaged u

Página 9

The controller shall have the ability to set the programmed occupied schedule time as the time at which the desired occupied temperature setpoin

Página 10

Packaged unit controller model dependent specifications: VZ7656R1000B: Up to two heating and two cool stages, single fan speed output, 0-10Vdc out

Página 11

BACnet Zone Controller VZ7260 Zone Controller – The zone controller shall be capable of controlling a local VAV analog damper actuator as well

Página 12

The zone controller shall have a binary input that can be configured as follows: BI1 Binary input no.1 configuration Default: None (None): No func