Objects Supported By Models: (VTR7300 Controllers & VRP5000W Wireless Repeater)
Please refer to the specific installation guide of each controller for a detailed overview on each property listed
Wireless Repeater
The wireless repeater (VRP5000W1000W) has been specifically designed to be used within a Viconics wireless ZigBee network. It is intended to be a low cost
additional communication component when some remote controllers are too far from the main mesh of Viconics devices and cannot communicate. The repeater will
enable the remote controllers to establish communication and will act as bridges to the main mesh. Furthermore, it does not need to be added to the database network
to lessen the resource required for the Jace & the station.
Object Name
Object Type
Object Property
VTR7300A5x00W
VTR7305A5x00W
VTR7350A5x00W
VTR7355A5x00W
Room Temperature
Numeric Writable
Present Value (R,W)




Outdoor Temperature
Numeric Writable
Present Value (R,W)




Room Humidity
Numeric Point
Present Value ®


Supply Temperature
Numeric Point
Present Value ®




Occupied Cooling Setpoint
Numeric Writable
Present Value (R,W)




Occupied Heating Setpoint
Numeric Writable
Present Value (R,W)




Stand-By Cooling Setpoint
Numeric Writable
Present Value (R,W)




Stand-By Heating Setpoint
Numeric Writable
Present Value (R,W)




Unoccupied Cooling Setpoint
Numeric Writable
Present Value (R,W)




Unoccupied Heating Setpoint
Numeric Writable
Present Value (R,W)




Dehumidification RH Setpoint
Numeric Writable
Present Value (R,W)


Occupancy Command
Enum Writable
Present Value (R,W)



