PARAMETER DETAILS SCREEN 2/7
Configuration Parameters Default Value Significance and Adjustments
Standby mode
Default value: Abs
Standby Mode
Choose which standby setpoints are used for control.
Abs: absolute Standby entered values are used for standby mode.
Offset: offset Occupied setpoints +/- Standby diff. used for standby
mode.
Standby diff.
Default value: 2 °C ( 3 °F )
Standby Difference
When Standby mode is Relative, standby setpoints are calculated as:
Standby cool = Cool setpoint + Standby diff.
Standby heat”= Heat setpoint - Standby diff.
Adjustable from 0.5 a 2.5 °C ( 1 - 5 °F )