VT8300 Series
User Interface Guide
BACNET NETWORK SETTINGS
BACnet network set-up screen shows when BACnet is detected in model. Select desired parameter and use up or down arrow to set
parameter to desired value.
254 value sets BACnet®
network Offline. Choose different
value to activate Online
Imperial or
Metric units
Language setting
Baud rate
settings
Displays BACnet status,
Offline or Online
PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
Comm address
Terminal Equipment Controller
networking address
Default value = 254
Range: 0 to 254
Communication Address
For BACnet® MS-TP models, the valid range is from 1 to 127.
Default value of 254 disables BACnet® communication for the Terminal
Equipment Controller.
Network units
Default value = Imperial
Measurement Units
(Imperial): network units shown as Imperial units.
(SI): network units shown as International Metric units.
Network lang
Default value = English
Language Settings
Choice of network language/object names transmitted over network.
All available choices: (English, French, and Spanish).
Baud rate
Default value = Auto
Baud Rate
(Auto): automatically detects BACnet® MS/TP baud rate.
Other choices: (115200, 76800, 57600, 38400, 19200, and 9600).