PARAMETER DETAILS SCREEN 1/7
Configuration Parameters Default Value Significance and Adjustments
UI 19
Universal input no.3 configuration
Default value = None
Universal Input No. 3
None: no function associated with input though input can be used
for remote network monitoring.
COC/NH: change over dry contact. Normally heat used for hot/cold
water or air change over switching in 2 pipe systems.
COC/NC: change over dry contact. Normally cool used for hot/cold
water or air change over switching in 2 pipe systems.
COS: change over sensor. Used for hot/cold water or air change over
switching in 2 pipe systems.
Occupancy cmd
Default value = Local
Occupancy Command
Loc Occ: occupancy is determined by local sequences.
Occupied: force occupied mode.
Unoccup: force unoccupied mode.