Parameter Variable Name Function
This configuration property defines the thermostat’s common
configuration parameters and their settings.
Valid Range and Default values:
Sub Name Valid Range Default value
01 password 0 to 1000 0
02 control type 0 = On/Off Control
1 = Floating Control
0 = On/Off
Control
03 floating actuator time 0.5 to 9 minutes (0.5
increments)
1.5 minutes
04 cycles per hour 3, 4, 5, 6, 7 and 8
CPH
4 CPH
05 reverse or direct acting
output
0 = Direct Acting (DA)
1 = Reverse Acting
(RA)
0 = Direct
Acting (DA)
06 temperature scale 0 = °C
1 = °F
°F
07 auto mode 0 = Not Active
1 = Active
1 = Active
08 temperature scale 0 = °C
1 = °F
°F
09 pipes number main out
config
2 = 2 pipe
4 = 4 pipe
4 pipe
10 sequence of operation
0 = Cooling Only
1 = Heating Only
2 = Cooling & Reheat
3 = Heating & Reheat
4 = Cooling/Heating 4
pipes
5 = Cooling /Heating
4 pipes & Reheat
1 = Heating
Only
11 fan menu 0 = Low-Med-High
1 = Low-High
2 = Low-Med-High-
Auto
3 = Low-High-Auto
4 = On-Auto
4 = On-Auto
12 heat maximum
setpoint
40 to 90°F
(4.5 to 32°C)
90°F (32°C)
13 cool minimum
setpoint
54 to 100°F
(12 to 37.5°C)
54°F (12°C)
14 calib room sensor ± 5°F (±2.5°C) 0°C
15 deadband 2, 3, 4 or 5 °F
(1 to 2.5°C)
2°F (1°C)
16 setpoint type 0 = Permanent
1 = Temporary
0
17 setpoint function 0 = Dual Setpoints
1 = Attached
Setpoints
0 = Dual
Setpoints
Thermostat
Common
Configuration
Parameters
network input config
UNVT_cfg_1_fcu_zn
nciCfg1FcuZn
18 temporary occ time 0, 1, 2, 3, up to 24
hours
2 hours