6 | VZ7656E1000W Installation Guide
TERMINAL, IDENTIFICATION AND FUNCTION
Wiring
Terminal Use
Description
1 Cool 2
Output for cooling / compressor stage
number 2.
2 Cool 1
Output for cooling / compressor stage
number 1.
3 - Fan
Output for the fan.
4 - 24 V ~ Hot
Power supply of controller, hot side
(Delivered from the RTU).
5 - 0 V ~ Com
Power supply of controller, common side.
Also used as reference for the analog BPD
output when used (Delivered from the RTU).
6- Heat Switch Leg
24 VAC switched leg for the heating stages.
If heating stages are part or RTU,
install a jumper across RC & RH.
If heating stages are part of separate
equipment with a different power
supply, feed external switched power
leg through RH without installing a
jumper across RC & RH.
7 Heat 1
Output for heating stage number 1.
8- Heat 2
Output for heating stage number 2.
9 By-pass damper
Local analog 0 - 10 VDC by-pass damper /
VFD output.
10 Economizer Output
0-10 VDC analog fresh air damper /
economizer output.
11 Static pressure
Local analog 0 5 VDC static pressure
input.
12 AI
0-10 VDC analog input for airflow transmitter
13 - RS
Return air temperature sensor input. If
sensor fails, controller will use the on-board
thermistor sensor to control if the
communication is lost.
14 - Scom
Reference input for DI 1, RS, OS & DS.
15 - OS
Outside air temperature sensor input.
16 - DS
Discharge air temperature sensor input.