Viconics VZ7260X Installation Guide Manual do Utilizador Página 1

Consulte online ou descarregue Manual do Utilizador para Para a casa Viconics VZ7260X Installation Guide. Viconics VZ7260X Installation Guide User Manual Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 38
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 0
1 | VZ7260W Series- Installation Guide
CONTENTS
Installation 2
Location 2
Installation 2
Theory of Operation 3
Features and benefits overview 3
Wireless System Overview 5
Terminal, Identification and Function 6
Wiring 6
Typical Applications 7
Main outputs wiring 7
Remote sensor accessories 11
CO2 sensor wiring 12
Configuring and Status Display Instructions 13
Status display 13
User interface 14
User configuration menu 14
Local keypad interface 15
Installer Configuration Parameter Menu 15
AI4 Input for CO2 Sensor 29
Referenced Operational Control Curves 30
Specifications Error! Bookmark not defined.
Drawing & Dimensions 38
VZ7260X5X00W
Zigbee™ Wireless Zone Terminal Equipment
Controller
Installation Guide
For Commercial Zoning Systems
July 27
th
, 2012 / 028-0329-R3
Vista de página 0
1 2 3 4 5 6 ... 37 38

Resumo do Conteúdo

Página 1 - Installation Guide

1 | VZ7260W Series- Installation Guide CONTENTS Installation 2 Location 2 Installation 2 Theory of Operation 3 Features and benefits overv

Página 2 - INSTALLATION

10 | VZ7260W Series- Installation Guide Mandatory RehtConf = 2 = On-Off Duct Reheat Only Set BO5 Time to 0= 15 minutes if using regular 24 VAC rel

Página 3 - THEORY OF OPERATION

11 | VZ7260W Series- Installation Guide Remote sensor accessories Model no. Description S3010W1000 Wall mounted temperature sensor S2000D1000 Duct m

Página 4

12 | VZ7260W Series- Installation Guide Wiring example of single remote room sensor: Wiring examples of 2 remote room sensors for averaging applicat

Página 5 - WIRELESS SYSTEM OVERVIEW

13 | VZ7260W Series- Installation Guide CONFIGURING AND STATUS DISPLAY INSTRUCTIONS Status display The Terminal Equipment Controller features a two

Página 6 - Wiring

14 | VZ7260W Series- Installation Guide USER INTERFACE User configuration menu • Unoccupied mode Override An Override can be made during an unocc

Página 7 - TYPICAL APPLICATIONS

15 | VZ7260W Series- Installation Guide Local keypad interface When left unattended for 45 seconds, the display will resume automatic status displa

Página 8 - 24 V~ Hot

16 | VZ7260W Series- Installation Guide Configuration Parameters Default Value Significance and Adjustments PswrdSet Configuration parameters menu

Página 9

17 | VZ7260W Series- Installation Guide When PAN ID is used with a range of 251 to 500, for (SA) Stand-Alone Systems In this application, the VZ76 co

Página 10 - Hot Water

18 | VZ7260W Series- Installation Guide When PAN ID is used with a range of 1 to 250, for (NS) Networked Systems In this application, any controller

Página 11 - Remote sensor accessories

19 | VZ7260W Series- Installation Guide Channel Channel selection Default value = 10 Conditional parameter to Wireless models (VZ7260CX5x00W) only

Página 12 - CO2 sensor wiring

2 | VZ7260W Series- Installation Guide INSTALLATION Remove the security screw on the bottom of Terminal Equipment Controller cover.  Open unit

Página 13 - Status display

20 | VZ7260W Series- Installation Guide Get From Controller Get From another device configuration utility Default value = 255 Range is: 1 to 255 Ent

Página 14 - USER INTERFACE

21 | VZ7260W Series- Installation Guide Lockout Keypad lockout levels Default value = 0 No lock 0 = No lock 1 = Low level 2 = Medium level 3 = High l

Página 15 - Local keypad interface

22 | VZ7260W Series- Installation Guide RehtConf Number of Reheat Stages and their applications Default: 1 = Modulating Duct Reheat Only 0 = None Z

Página 16

23 | VZ7260W Series- Installation Guide 5 = Duct heater & On-Off/Pulsed perimeter reheat (All electric) Zone will operate in VAV heating or cool

Página 17

24 | VZ7260W Series- Installation Guide AO2RA/DA RA/DA Reverse acting or Direct acting actuator signal for Reheat 1 Analog output signals Default:

Página 18

25 | VZ7260W Series- Installation Guide BO5 Time Sets the time base for the ON-Off reheat output if used Default: 0 = 15 minute Valid only if reheat

Página 19

26 | VZ7260W Series- Installation Guide St-By HT Stand-by heating setpoint Default: 65 °F (18°C) Stand-by heating setpoint adjustment. This setpoin

Página 20

27 | VZ7260W Series- Installation Guide Pband Proportionnal band setting Default is : 3 Adjust the proportional band used by the controller PI contr

Página 21

28 | VZ7260W Series- Installation Guide Min Pos Zone damper minimum position Default : 10% Sets the minimum position of the damper. 0 to 100% (Increm

Página 22

29 | VZ7260W Series- Installation Guide CL Perfo Controller’s cooling performance Default value: None Not a configuration parameter. Only displays t

Página 23

3 | VZ7260W Series- Installation Guide 10. Insert each wire according to wiring diagram. 11. Gently push excess wiring back into hole (fig. 3). 12.

Página 24

30 | VZ7260W Series- Installation Guide REFERENCED OPERATIONAL CONTROL CURVES RehtConf = 0 = None VZ7260F Series: Analog Outputs VZ7260C Series: Fl

Página 25

31 | VZ7260W Series- Installation Guide RehtConf = 1 = Analog Duct Reheat Only VZ7260F Series: Analog Outputs VZ7260C Series: Floating Outputs

Página 26

32 | VZ7260W Series- Installation Guide RehtConf = 2 = On-Off Duct Reheat Only VZ7260F Series: Analog Outputs 10 RTC in Cooling mod

Página 27

33 | VZ7260W Series- Installation Guide VZ7260C Series: Floating Outputs RTC in Cooling modeRehtConf = 2 ( On/Off Duct Reht Only)B

Página 28

34 | VZ7260W Series- Installation Guide RehtConf = 3 = On-Off Perimeter Reheat Only VZ7260F Series: Analog Outputs VZ7260C Series: Floating Outputs

Página 29 - AI4 INPUT FOR CO2 SENSOR

35 | VZ7260W Series- Installation Guide RehtConf = 4 = Analog Duct Reheat & On-Off Perimeter Reheat VZ7260F Series: Analog Outputs VZ7260C Ser

Página 30 - RehtConf = 0 = None

36 | VZ7260W Series- Installation Guide RehtConf = 5 = Pulsed Duct heater & On-Off/Pulsed perimeter reheat (All electric) VZ7260C Series: Floatin

Página 31 - BO5 = Off

37 | VZ7260W Series- Installation Guide SPECIFICATIONS Terminal Equipment Controller power requirements: Operating conditions: Storage conditions:

Página 32 - AO2 = Off

38 | VZ7260W Series- Installation Guide DRAWING & DIMENSIONS Viconics Technologies Inc. 9245 Langelier Blvd. I St-Leon

Página 33 - BO3-BO4 = Off

4 | VZ7260W Series- Installation Guide • PIR and Stand-by setpoints supported. • Local keypad lockable. • PI time proportioning algorithm. • Aux

Página 34 - AO2 = 0%

5 | VZ7260W Series- Installation Guide WIRELESS SYSTEM OVERVIEW Viconics VZ7260X5x00W Zone controllers are used in conjunction with the VZ7656X1000W

Página 35 - Temperature increase

6 | VZ7260W Series- Installation Guide TERMINAL, IDENTIFICATION AND FUNCTION Wiring Terminal Use Terminal Identification VZ7260F Terminal Identifica

Página 36

7 | VZ7260W Series- Installation Guide TYPICAL APPLICATIONS Main outputs wiring VAV Damper Wiring VAV Damper and Analog Reheat Wiring VAV Dampe

Página 37 - SPECIFICATIONS

8 | VZ7260W Series- Installation Guide Mandatory RehtConf = 0 None Pressure dependent VAV cooling or heating system with central changeover Manda

Página 38 - DRAWING & DIMENSIONS

9 | VZ7260W Series- Installation Guide Pressure dependent VAV cooling or heating system with local On-Off perimeter reheat and central changeover M

Comentários a estes Manuais

Sem comentários