VTR8300 Series
11
User Interface Guide
Viconics Technologies Inc. I Small Building Systems I 9245 Langelier Blvd. Saint-Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I www.viconics.com
028-6045-01 April 2014
© 2014 Viconics Technologies. All rights reserved.
PARAMETER DETAILS (CONT'D)
Configuration parameters
default value
Significance and adjustments
RBI 2
Remote Binary input
no.2 configuration
Default value = None
(None): No function will be associated with the input. Input can be used for
remote network monitoring.
(Filter): "Filter alarm" will be displayed on the Terminal Equipment Controller
LCD screen when the input is energized. It can be tied to a differential
pressure switch that monitor filters.
Contact opened = No alarm
Contact closed = Alarm displayed
(Service): "Service alarm" will be displayed on the Terminal Equipment
Controller LCD screen when the input is energized. It can be tied in to the
AC unit control card, which provides an alarm in case of malfunction.
Contact opened = No alarm
Contact closed = Alarm displayed
Occupancy cmd
(Loc Occ): Occupancy is determined by local sequences
(Occupied): Force occupied mode
(Unoccup): Force unoccupied mode