14
Parameter Variable Name Function
This configuration property defines model number and software
version of the thermostat
Valid Range and Default values:
Sub Name Valid Range Default value
01 Thermostat Model 11 = VT7600A
12 = VT7600H
10 = VT7600B
09 = VT7605B
02 = VT7652A
06 = VT7652B
01 = VT7656B
04 = VT7652H
Depend on model
being used
Thermostat’s
model numbe
network input config
UNVT_model_info_2
nciSccModel
02 Software Version Unsigned short Thermostat dependent
Maximum
Send Time
network input config
SNVT_time_sec
nciSendHrtBt
This configuration property defines the maximum period of time that
expires before the specified network variable outputs will automatically
be updated
Valid Range: 0 sec. To 6553.4 sec.. Setting nciSendHrtBt to 0
disables the Send Heartbeat mechanism.
Default Null Value : 0.0 sec (no automatic update)
Minimum
Send Time
network input config
SNVT_time_sec
nciMinOutTm
This configuration property defines the minimum period of time
between automatic network variable outputs transmissions.
Valid Range: 0 sec. to 6553.4 sec.. Setting nciRcvHrtBt to 0 disables
the Minimum Send Time mechanism.
Default Null Value : 0.0 sec (no minimum send time)
Minimum
Receive
Time
network input config
SNVT_time_sec
nciRcvHrtBt
This configuration property is used to control the maximum time that
elapses after the last update to a specified network variable input
before the Space Comfort Controller starts to use its default values.
Valid Range: 0 sec. to 6553.4 sec.. Setting nciRcvHrtBt to 0 disables
the Receive Heartbeat mechanism.
Default Null Value : 0.0 sec (no failure detected)
Hardware or
Software
revisions
network input config
SCPT_maj_ver
nciMajVer
This configuration property defines the major module software
revisions.
Valid Range: 0 to 255
Hardware or
Software
revisions
network input config
SCPT_min_ver
nciMinVer
This configuration property defines the minor module software
revisions.
Valid Range: 0 to 255
Location
Label
network input config
SNVT_str_asc
nciLocation
This configuration property can optionally be used to provide more
descriptive physical location information than can be provided by the
Neuron Chip’s 6 byte location string. The location relates to the object
and not to the node.
Valid Range: Any NULL terminated ASCII string of 31 bytes total length