9 | VZ7260B Series - Installation Guide
Pressure dependent VAV cooling or heating system with local On-Off
perimeter reheat and central changeover
RehtConf = 3 =
On-Off Perimeter
Reheat Only
Set BO5 Time to
0= 15 minutes if
using regular 24
VAC relays
Set BO5 Time to
1= 10 seconds if
using 24 VAC
Solid State Relays
(SSRs) for
proportional control
RehtConf = 3 =
On-Off Perimeter
Reheat Only
Set BO5 Time to
0= 15 minutes if
using regular 24
VAC relays
Set BO5 Time to
1= 10 seconds if
using 24 VAC
Solid State Relays
(SSRs) for
proportional control
Pressure dependent VAV cooling or heating system with local On-Off duct
reheat and central changeover
RehtConf = 2 =
On-Off Duct
Reheat Only
Set BO5 Time to
0= 15 minutes if
using regular 24
VAC relays
Set BO5 Time to
1= 10 seconds if
using 24 VAC
Solid State Relays
(SSRs) for
proportional control
Tri-State Floating VAV Actuator
Positions Adjusted at Controller