VTR8300 Fan Coil ControllerApplication Guide
20
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: ( 514) 321-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
The PIR can maximize
your energy saving from
10-30% by relaxing
temperature set points in
unoccupied zones during
scheduled periods.
Typical Savings of 10-30%
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
0 2
4 6 8 10 12 14 16 18 20 22 24
Time of Day (EST)
Energy Usage (KWh)
0%
10%
20%
30%
40%
50%
Saving Percentage
Typical Consumption PIR Thermostat Consumption Savings
APPENDIX A - PASSIVE INFRA-RED (PIR) MOTION DETECTOR COVER SPECIFICATIONS
Initially, the controller is in Stand-by mode. Stand-by setpoints are used at the controller. As soon as the
PIR detects motion, the Occupancy status switches to Occupied and the Stand-By Time timer is reset. The
Occupied setpoints are used. If no motion is detected in the room for the entire Stand-By Time duration
(adjustable parameter), the room then switches to Stand-by mode and stand-by setpoints are used. While in
Stand-by mode, if no motion is detected for the entire Unoccupied Time period (adjustable parameter), the
room switches to Unoccupied mode and uses its Unoccupied setpoints. While in Stand-By or Unoccupied
mode, any motion will switch the room back to Occupied mode.
PIR cover sequence of operation
Typical Detection Pattern for PIR Lens
Energy savings
20
O
20
O
20
O
20
O
40
O
A
B
B
C
C
Horizontal Angles (Typical)
Transverse motion: 4-5 ft/s
/ 1.5 m/s
Recommended installation
height for PIR sensor:
4 - 5 ft. / 1.2-1.5 m
Sensor Ranges
A = 20 ft. / 6.1 m
B = 14 ft. / 4.3 m
C = 11 ft. / 3.4 m
Center
30
O
Vertical Angle (Typical)
Center